Input Signal Range:
4 – 20 mA
20 – 100 kPa
Maximum Air Supply:
10 Bar g
Minimum Air Supply:
2.0 Bar g
Maximum Flow Capacity:
17.5m3/h
Air Quality:
Air Supply must be dry, oil and dust free to ISO 8573-1 Class 3
Stroke Range:
Rotary: 90° nominal
Linear: 6 mm – 1200 mm (55° nominal)
Action:
Double-acting feld reversible (can be configured for single-acting)
Operating Temperature:
-20°C to 85°C
Steady State Air Consumption:
6 – 8.0 l/min
Air Connections:
1/4” NPT
Cable Gland:
M20 x 1.5 (Electropneumatic Only)
Electrical Connections:
Screw Terminals for 0.1 to 2.0mm² wire
Enclosure Rating:
IP64 – on request : Certification Body – SABS
Characteristics:
Linear or Equal Percent
Mass:
1.5kg (P/P) 2.0kg (I/P)